PLLD Shutdown alarm
The tank monitor shut off one fuel line's pump.
It follows a failed line leak test or another alarm.
The pumps on that line can't sell until it clears.
Need a tech for this?
Request a techCheck this first
On the screen: PLLD SHUTDOWN ALARM
- Print the alarm report: it names the alarm behind it.
- Check that the tank on that line has fuel.
- Look for fuel at the dispensers and the tank sump.
When to call a tech
- The tank has fuel and the line stays off.
- The report shows a failed line leak test.
- You see or smell fuel.
Not to be confused with
- Fuel Out: the tank is nearly empty. A delivery fixes it.
Good to know
- The line's 3 gph test runs right after the last sale ends.
- An empty tank can fail the line test too.
- Federal rule: report a suspected leak within 24 hours.
- Your state can set a stricter deadline.
Who can fix it
- A tech certified on Veeder-Root consoles.
- Texas: line and tank repairs need a TCEQ-registered contractor.
Typical cost
| Job | Price | Source |
|---|---|---|
| Tech labor, weekdays | $210 an hour | Washington State contract 12825, 2026 |
| Tech labor, weekends | $420 an hour | Washington State contract 12825, 2026 |
Prices from public bids, contracts and price lists, not quotes.
Need a tech?
One request. Up to 4 licensed techs call.
Request a techRelated
Sources: Veeder-Root 577014-243, Rev C (2026), p. 9, Veeder-Root 576013-610, Rev AC (2013), p. 29-10, Veeder-Root 577013-727, Rev B (2000), p. 2, 40 CFR 280.50, reporting suspected releases, TCEQ: licensed tank contractors (RG-475c), Veeder-Root: certified technician training, Washington State contract 12825.