Red Jacket IQ control box: red light codes

Count the red flashes. Each count means something different.

For the IQ box that runs a Red Jacket submersible pump.

Updated October 18, 2026

To silence it

  • Press Reset/Cal on the side until one green flash shows.
  • That turns off the red light. It doesn’t fix the cause.
  • Don’t hold it 10 seconds: that starts a recalibration.

Red light codes

Red light codes: what each message means and what to do
On the screenWhat it meansWhat to doManual
1 red flashThe box was never calibrated, so it can’t fully protect the pump.Call a tech.D051-330, p. 16
2 red flashesToo much current: a wiring short or a jammed pump.Stops salesCall a tech.D051-330, p. 17
3 red flashesThe pump ran dry. The fuel is below the pump.More on this alarmStops salesGet a delivery. It restarts by itself.D051-330, p. 17
4 red flashesToo little current. The pump won’t run.Stops salesCall a tech.D051-330, p. 17
5 red flashesA switch setting or the cable between boxes is wrong.Call a tech.D051-330, p. 17
6 red flashesThe power dipped below 200 V. The pump keeps running.Call a tech.D051-330, p. 17
7 red flashesThe box is in Bypass mode, so it isn’t protecting the pump.Call a tech.D051-330, p. 17
8 red flashesThe pump ran over 6 hours straight. A nozzle may be off its hook.Check every nozzle is hung up.D051-330, p. 18